- Order number: E_10175
- Additional Text: AKCP Dual Sensor - Temperature and Humidity Sensor
Dual sensor, 2 sensors on one port!
In situations where both temperature and humidity can be critical you can keep up to speed on the current conditions using this sensor. Combining temperature and humidity into the one sensor frees up an additional intelligent sensor port on your base unit.
- Monitors temperature and humidity on a single intelligent sensor port
- Own SNMP OID for data collection via a network
- Temperature measurement from -40ºC – +75ºC
- Relative Humidity measurement from 0% – 100%
- Powered by base unit, no additional power needed
Setup is simple with the AKCP sensorProbe and securityProbe autosense function. Once plugged into the intelligent sensor port the base unit automatically detects the sensors presence and configures it for you. All you need to do is set your thresholds for low and high warning and critical parameters. The built in graphing function of the base unit gives you a pattern of temperature or humidity trends over time.
This sensor is available in 2 versions
- A fixed 1ft cable length version
- With free 5ft cable - extended with Cat-5 Cable up to 300 Meters
Certification
Our Single Port Temperature / Humidity Sensor is calibrated using dedicated equipment which is calibrated according to ISO/IEC 17025 and calibrated by comparison against natural standards, natural physical constants, consensus standards, or by ratio type measurements using self-calibrating techniques.
Standards incorporated to establish this comparison are NIST and NPL traceable.Our Single Port Temperature / Humidity Sensor comply with RoHS and WEEE requirements. There is no substance to be declared.
Notes of the technical editor:
Please note that if the new AKCP temperature sensor is used with older sensorProbe and securityProbe remote environmental monitoring systems (until September 2017), a firmware update may be necessary.
The obsolete securityProbe remote monitors with old PXA chipset are not supported by this sensor!
Temperature
Measurement Range Celsius : | -40°C to +75°C |
Measurement Resolution Celsius : | 1°C |
Measurement Accuracy Celsius : | Maximum ±2.3 at -40ºC, minimum ±0.4 at +25ºC and ±1.7 at +75ºC |
Measurement Range Fahrenheit : | -40°F to +167°F |
Measurement Resolution Fahrenheit : | 1°F increments |
Measurement Accuracy Fahrenheit : | Maximum ±4.1 at -40ºF, minimum ±0.9 at +25ºC and ±4 at +167ºF |
Humidity
Measurement range : | 0 to 100% Relative humidity |
Resolution : | 1% |
Accuracy at : | 25°C ±3% |
Communications cable : | UTP Cat 5 cable |
Power source : | Powered by the sensorProbe. No additional power needed |
Power Consumption : | Typical 7.25 mWatt, 1.45mA |
Sensor element wettable without damage | |
sensorProbe auto detects the presence of the dual sensor | |
Up to 2 dual sensors per sensorProbe2, 8 per sensorProbe8 and securityProbe | |
Important Note: | The fixed one foot type or TMP01 and THS01 are not designed to be extended. If you need to extend these sensors then you need to use the TMP00 or THS00 (remote type). Compatible with AKCP sensorProbe and securityProbe IT monitoring devices from September 2017. A firmware update may be required. Older securityProbe IT monitors with PXA chipset are not supported. |